Real-Time Fault Location Using the Retardation Method

نتاج البحث: نشر في مجلةمقالةمراجعة النظراء

1 اقتباس (Scopus)

ملخص

A new method for short-circuit fault location is proposed. The method is based on instantaneous signal measurement and its first and second derivatives, which are the novel elements of the current approach. The derivatives allow associating a precise time stamp to the occurrence of the fault. Due to retardation phenomena, the difference between the times in which a signal is registered in two detectors can be used to locate the fault. We offer several mathematical models to describe the fault. Although a description of faults in terms of a lumped circuit is useful for elucidating the methods for detecting the fault, this description will not suffice to describe the fault signal propagation; hence, a distributed models is needed, which is given in terms of the telegraph equations. Those equations were used to derive a transmission line transfer function, and an exact analytical description of the fault signal propagating in the transmission line was obtained. The analytical solution was verified both by numerical simulations and experimentally.

اللغة الأصليةالإنجليزيّة
رقم المقال980
دوريةElectronics (Switzerland)
مستوى الصوت11
رقم الإصدار7
المعرِّفات الرقمية للأشياء
حالة النشرنُشِر - 1 أبريل 2022

بصمة

أدرس بدقة موضوعات البحث “Real-Time Fault Location Using the Retardation Method'. فهما يشكلان معًا بصمة فريدة.

قم بذكر هذا