The paper describes preliminary testing transformer oil of the two kinds - "fresh" (unused) and "used" for a long period in real-world conditions. The experimental setup assembled for testing is based on the cut-off rectangular waveguide with plastic tube filled with the tested oil. The insertion losses of the sensor are measured by Vector Network Analyzer Agilent PNA-L N5230C. There is observed a shift of resonance curve of the "used" oil respectively the "fresh" one toward low frequency. It can be interpreted as increasing a real part of dielectric constant of the "used" oil in comparison with its "fresh" counterpart. Also, the "used" oil has higher insertion loss that is caused by increasing its loss tangent compared with the "fresh" oil.

اللغة الأصليةالإنجليزيّة
عنوان منشور المضيف2010 IEEE 26th Convention of Electrical and Electronics Engineers in Israel, IEEEI 2010
الصفحات6-8
عدد الصفحات3
المعرِّفات الرقمية للأشياء
حالة النشرنُشِر - 2010
الحدث2010 IEEE 26th Convention of Electrical and Electronics Engineers in Israel, IEEEI 2010 - Eilat, إسرائيل
المدة: 17 نوفمبر 201020 نوفمبر 2010

سلسلة المنشورات

الاسم2010 IEEE 26th Convention of Electrical and Electronics Engineers in Israel, IEEEI 2010

!!Conference

!!Conference2010 IEEE 26th Convention of Electrical and Electronics Engineers in Israel, IEEEI 2010
الدولة/الإقليمإسرائيل
المدينةEilat